JN22-36 Indoor earthing switch
JN15-12 Indoor earthing switch is applicable for three-phase AC power system of ra…
JN22-36 Indoor earthing switch

JN22-36 Indoor earthing switch

Detailed description

  • Description
  • Technical data

JN15-12 Indoor earthing switch is applicable for three-phase AC power system of rated voltage up to 7.2KV~40.5KV and frequency 50/60 Hz, it widely used in many fields such as power plant, transformer substation, petrol chemical industry, metallurgy, manufacturing industry, airport, residential area, etc, for mounted at in frequency operation service indoor  air insulating switchgear like tyoe KYN28 or KYN96, ABB type ZS series,etc. The application of it and its expending products can fully meet the requirement of GB, DL, IEC, DIN, VDE ad well as standards of other advanced industrial countries.

++++Swrvice environment:

a)Air temperatue: Maximum temperature:+40℃; Minimum temperature :-35℃

b)Humidity:Monthly average humidity 95%; Daily average humindity 90%.

c)Altitude above sea level: Maximum installation altitude:2500m

d)Ambient air not apparently polluted by corrosive and flammable gas, vapor, etc.

e)No frequent violent shake

No.

Item

Unit

Parameter

 

1

Rated voltage

KV

36

 

2

Rated frequency

Hz

50/60

 

3

1min power frequency withstand voltage

KV

95

 

4

Lightming impulse withstand voltage

KV

185

 

5

Short time withstand current(4s)

KA

31.5

 

6

Mechanism life

times

2000


Best solution for your power!