LW36-145kV outdoor SF6 circuit breaker
Specifications:ROCKWILL developedLW36-145 typeoutdoor SF6 gas circuit breaker usin…
LW36-145kV outdoor SF6 circuit breaker

LW36-145kV outdoor SF6 circuit breaker

Detailed description

  • Description
  • Technical data

Specifications:

ROCKWILL developed LW36-145 type outdoor SF6 gas circuit breaker using modern processing technology and computer-aided design techniques, combined

with the latest generation of spring bodies and the advantages of a permanent institution. Its pursuit of high reliability, easy to maintain design concepts to create ageneration of superior product, is the most reliable electric power system and the best option.

ROCKWILL all series switches meet the following criteria:

ANS/IEEE C37.60/IEC 62271-100(GB1984-2003 China standard)

GBT11022-1999 China Standard
IEC 60255-11
IEC 60255-21-1 Class I
IEC 60255-21-2 Class I
IEC 60255-21-3 Class I
IEC 60255-22-1 Class III
IEC 60255-22-2 Class IV
IEC 60255-22-3 Class III
IEC 60255-22-4 Class IV

Using of the enviroment:

Ambient temperature:-40℃~+40℃, the daily average temperature:25℃;

Altitude:≤ 3000m(in excess of the value of technical discussions with the divisionI);

Wind speed:35m/s;

Earthquake intensity: not more than 8 degrees;

Degree of ambient air contamination level not greater than:III level;

Daily average ambient air relative humidity≤95%, on average≤90%;

Saturated vapor pressure of daily mean values≤ 2.2*10^(-3)MPa, on average≤1.8*10^(-3)MPa;

More about the use of environment conditions, please consult with the manufacturer.


Note: For short circuit breaking current & rated current is optional by clients.

No.

Item

Unit

Data

1

Rated voltage

KV

145

2

Rated frequency

Hz

50/60

3

Rated current

A

3150

4

1min power frequency withstand voltage

KV

265

5

Lingthning impluse withstand voltage(peak value

KV

650

6

5 min power frequency voltage at zero gas pressure

KV

109

7

Rated short circuit breaking current

KA

80...100

8

Rated out-of-phase breaking current

KA

10

9

Rated cable(line) charging breaking current(peak)

A

50

10

Rated gas pressure

MPa

0.5

11

Main loop resistance

≤45

12

Operation sequence

O-0.3s-CO-180s-CO

13

SF6 gas leakage rate(per year)

%

≤1

14

Moisture content(V/V)

ppm

≤150

15

Across the open contacts

mm

≥3950

Creepage distance

TO earth

≥3950

16

Mechanical life

times

10,000