RMR-40.5 Full gas insulated RMU
GeneralRMR-36/40.5kV is completely insulated SF6 Gas insulated Switchgear.This pro…
RMR-40.5 Full gas insulated RMU

RMR-40.5 Full gas insulated RMU

Detailed description

  • Description
  • Technical data

General

RMR-36/40.5kV is completely insulated SF6 Gas insulated Switchgear.

This product is in conformity with the standards the GB/IEC standard and the design of a high safety combined switch cabinets.

The system of RMR-36/40.5kV of combined switch cabinets can be divided into three kinds of unit cabinet:

  • 3 position cable connection unit (Cable switch unit), additional live shows and configuration of surge arresters and grounding fault component. Code C
  • 3 position switch and fuse tripping system and earthing switch interlock system fuse combined electrical unit (Fuse combination unit), additional live shows and configuration of surge arresters and grounding fault component. Code F
  • 3 position switch and vacuum circuit breaker combined appliances unit (Vacuum circuit breaker unit), additional current transformer, live shows and configuration of surge arresters and grounding fault component. Code V

The combination of the current transformer and the microcomputer protection to constitute the basic circuit protection function.

Microcomputer protection using passive protection and CT electric no need of additional PT power supply Reference standard:

----IEC62271-200               ----IEC62271-100      ----GB3804-2004              ----GB3906-1991 ----GB16926-1997             ----GB/T11022-1999

Remark:

Fuse combined electrical follow IEC 60420

VCB unit according to IEC 62271-100/GB1984-2003

Service environment

a) Air temperature: ±40℃; Daily average ≤25°C

b)Altitude above sea level: Maximum installation altitude: 4000m

c)Wind: less than 35m

d)Earthquake intensity: no more than 8 degrees;


More details pls consult with us!


No

Item

Unit

Data

1

Rated voltage

kV

24/36

2

Power Frequency withstand voltage

Dry

60/70/80/95

Wet

Lightning Impulse withstand Voltage

(peak value)

125/150/170/185/200

3

Rated Current

A

630/1250/2500

4

Rated short circuit breaking current (peak)

kA

20/25(V) 31.5(F)

5

Rated closed-loop breaking current

A

630/1250(C)

6

Rated cable charging interrupting current

A

50(C)

7

Rated line cable charging interrupting current

A

10(C)

Rated off circuit transformer breaking current

A

16

8

Rated making current (peak)

kA

50(63/80)/2.5(main switch/grounding)

9

Rated  withstand current (peak)

10

Rated short time withstand current

16/20/25/31.5

11

Rated short time withstand time

S

3/4

12

Mechanical life

times

C/F(2000)V(10,000)

13

Main busbar

A

630/1250/2000/2500

Best solution for your power!