RSW pole mounted vacuum sectionalizer
General:Pole-mounted load-break switch(Pole-LBS) applies up to 36KV 400/630A, 50Hz…
RSW pole mounted vacuum sectionalizer

RSW pole mounted vacuum sectionalizer

Detailed description

  • Description
  • Technical data

General:

Pole-mounted load-break switch(Pole-LBS) applies up to 36KV 400/630A, 50Hz pole-LBS associated with a state-of- the-art controller. This SF6 gas-insulated switch can corporate with the distribution automation system, and also isolate section of distribution line from the control center.

A simple pole-mounting arrangement contribute to quickand low cost installation, and the swtch can be operated manually with a electronic controller. Electronic controller is contained in a stainless steel cabinet for an all weather environmental conditions.Remote monitoring and control can also b prvided mounting wire or wireles modem in a cabinet.


Service environment:

a)Air temperature: Maximum temperature:+85℃; Minimum temperature:-45℃.

b)Humidity:Monthlu average humidity 95%; Daily average humidity 90%.

c)Altitude above sea level:Maximum installation altitude:2500m or higher.

d)Ambient air not apparently polluted by corrosive and flammable gas, vapor, etc.

e)No frequent violent shake.


Descriptions

Rating

 

 

Rated voltage

12KV/24KV/36KV

 

 

Rated current

630A

 

 

Rated frequency

50Hz

 

 

Rated short-time current

20KA(r.m.s),4 sec.

 

 

Rated making current

50KA(peak),3 times

 

 

Load current breaking

400/630A, 30 times

 

 

Cable charging current breaking

25A, 10times

 

 

Line charging current breaking

1.5A, 10 times

 

 

Magnetic current breaking

22A, 10 times

 

 

Main contact

No voltage breaking

Ground contact

5000 times

 

2000 times

 

 

Closing time

Operating timings

Opening time

1.0 sec.

 

1.0 sec.

 

 

Dry condition, 1minute

Power-frequency withstand voltage

Wet condition, 10sec.

50KV/60KV/85KV

 

34KV/50KV/70KV

 

 

Impulse withstand voltage(1.2*50us)

95KV/150KV/170KV

 

 

Rated voltage

Controller          Power frequency withstand voltage

Impulse withstand voltgae(1.2*50us)

220kv

 

 

2KV rms,minute

 

 

6KV peak

 

 

Best solution for your power!