Important news: No.1. Rockwill attend Dubai MEE Exhibition 2020 No.2: Rockwill's pole mounted load break switch passed the KEMA type test!
36kV Drawable type VCB
General: VD4 high-voltage indoor vacuum circuit breaker is applicableforthree-phas…
36kV Drawable type VCB

36kV Drawable type VCB

Detailed description

  • Description
  • General Principals
  • The dimension of VD4-36
  • Technical data


General:
VD4 high-voltage indoor vacuum circuit breaker is applicableforthree-phase  AC power system of rated voltage up to 36kV and frequency 50/60HZ,widely used in many fields such as power plant, transformer substation, petrol chemical industry , metallurgy , manufacturing industry , airport, residential area, etc.,to control and protect the electric equipment, especially , It is usedforthe occasionthat needs infrequent operati on at rated current or multi-breaking short circuit current, may be mounted in the indoor air insulating switchgear like type KYN61 or AMS,  ABB type ZS3.2 series, etc. This circuit breaker is made with mature  APG technology . The application of VD4 terminal buffer guarantees the indoorterminal is ever more reliable in nay operation environment. VD4 can fully meet the requirement of GB, DL, IEC, DIN, VDE as well as standards of other advanced industrial countries.


Service environment:
a) Airtemperature: Maximumtemperature: +40℃; Minimumtemperature:-25℃
b) Humidity: Monthly average humidity 95%; Daily average humidity 90%.
c) Altitude above sea level: Maximum installation altitude: 2500m
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) Nofrequent violent shake


Note: For short circuit breaking current & rated currentis optionalby clients.



General Principals

VB( G) - 40. 5 type series of indoor highvoltage vacuum circuit breaker independently developed by our company is the leading domestic level of a new generation of 12kV vacuum circuit breaker, Its main feature is that the main circuit is installed

in the full sealed three- phase insulating cylinder the operation mechanism and the main circuit was of before and after layout. The operating mechanism is new- typespring one, which is independently researched and developed by my company, has the advantages of simple structure,reliable action


Standard

Every technical parameter VB(G)-40.5 type series of high- voltage vacuum circuit breaker is completely complied with GB1984、GB/T11022 ,China power Industry standard DL 403, at the same time also meet the standard,IEC62271-100 IEC56 and the related standard provisions of other major industrialized countries.


Test

VB( G) - 40. 5 type series of indoor high voltage vacuum circuit breaker has passed the following tests to ensure the security of operation.
·Type tests: power frequency withstand voltage, lightning impulse withstand voltage, temperature rise, short time and peak withstand current, short circuit current switching capability mechanism life etc.
·Factory routine test: The mechanical performance test, the main circuit power frequency withstand voltage test, auxiliary and control circuit insulation performance test, the main loop resistance test, interlock operation test,mechanical and electrical operation test.


Application range

VB( G) - 40. 5 type series of indoor high voltage vacuum circuit breaker can be widely used in Power plant, power network, metallurgical, petrochemical, city infrastructure such as airports, buildings, subway project.
VB- 40. 5 series of indoor high voltage vacuum circuit breaker in the distribution system can be applied to the control and protection of cables, overhead transmission line, transformer, motor, generator, and capacitor bank.


Safety of operation
VB- 40. 5 series of indoor high voltage vacuum circuit breaker owns perfect mechanical & electrical interlocking device, it is also with high operation reliability and service life, matching with the suitable switchgear to complete safe distribution function, ensure the safety of the operator and the equipment.


No

Item

Unit

Parameter

1

Rated voltage

kV

36

2

Rated f requency

Hz

50/60

3

Rated current

A

630, … 2500A

4

1min Power f requency withstand voltage

kV

95

1 18

5

Lightning impulse withstand voltage

kV

185

215

6

Rated short circuit breaking current (peak)

kA

50/63/80

7

Rated short breaking current

kA

20, …31.5

8

Rated short circuit making current (peak)

kA

50/63/80

9

Rated cable(line) charging breaking current

A

50 and 10

10

Rated single capacitor bank switching current

A

400

11

Rated withstand current (peak)

kA

50/63/80

12

Short time withstand current (4s)

kA

20, …31.5

13

Mechanism life

times

10000