Pole mounted load break switch
Pole mounted Load break switch - Normal application by a Manual operation mechanis…
Pole mounted load break switch

Pole mounted load break switch Pole mounted load break switch

Detailed description

  • Description
  • Technical data of pole mounted load break switch
  • 15kV IEC/ANSI
  • 27kV IEC/ANSI
  • 38kV IEC/ANSI
  • Mobile APP software GPRS/GSM/WIFI/BLUETOOTH

Pole mounted Load break switch

- Normal application by a Manual operation mechanism

- With Motorized can be upgraded to Sectionalizer


- Pole mounted SF6 Gas insulated load break switch (Pole mounted switch disconnector) type RPS-12/27/38-20 is suitable for the rated voltage up to 40.5kV,rated current 400A-630A, 50/60Hz power system.

-RPS type polemount LBS is SF6 breaking on load break switch, ie. on load switch disconnector.
Rated voltage: up to 40.5 kV
Rated current: 400 to 630 A
Insensitive to the environment.

Options:

E2/E3

Manual or remote control

CT/PT/VS
Gas pressure guage

Low pressure lockout

SCADA capabilities
etc...


DOWNLOAD: RPS SF6 Manual Load Break Switch

Motorized operation type gas LBS Sectionalizer

● Summary
ROCKWILL® Electric strives to bring our customers the latest technology and competitive pricing and best service for distribution automatic.
RPS is an SF6-insulated, outdoor pole mounted load break switch family for overhead lines and specifically designed for use in modern remote controlled distribution automation systems. The RPS offers reliable maintenance free operation even in the most demanding climatic conditions including salt laden atmospheres, corrosive industrial pollution, snow and ice. It has excellent load breaking and fault making capacity and satisfies the isolation requirements specified for load break switch. The earthed metal tank prevents all possible leakage currents across an open switch. RPS can be manually operated or motor operated for local and remote electric control, upgraded.
Service environment
1.Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃
Humidity: Monthly average humidity 95%; Daily average humidity 90% .
Altitude above sea level: Maximum installation altitude: 2500m or more higher.
Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. No frequent violent shake
Offering
With optional classes for rated current range:
--Type RPS 15, Rating6-20 kV with 400A, 16 kA up to 1250A, 20kA;
--Type RPS 27, Rating22-27 kV with 400A, 16 kA up to 1250A, 20kA;
--Type RPS 38, Rating30-40.5 kV with 400A, 16 kA up to 1250A, 20kA;
With optional classes for different grid application installation:
Section function (Section)
50 Instantaneous/Definite-Time Overcurrent(P.OC)
51 Phase Time-Overcurrent(P.Fast curve/P.Delay curve)
Overload (N.Fast curve/N.Delay curve)
50N Residual Ground Instantaneous/Definite-Time Overcurrent(G.OC)
51N Residual Ground Time-Overcurrent (G.Fast curve/G.Delay curve)
50SEF Sensitive Earth Fault (SEF)
51c Cold Load(Cold load)
TRSOTF Switch-Onto-Fault(SOTF)
59 Over Voltage(L.Over volt)
27 Under Voltage (L.Under volt)
Monitoring Functions:
Primary/Secondary Phases and Earth Currents
Direction
Primary/Secondary Line and Phase Voltages
Apparent Power and Power Factor
Real and Reactive Power
Historical Demand Record
Positive Phase Sequence Voltage & Current
Negative Phase Sequence Voltage & Current
Zero Phase Sequence Voltage
Frequency
Binary Input/Output status
Trip circuit healthy/failure
Time and date
Fault records
Event records

●Time-Overcurrent Curves


The following information describes the curve timing for the curve and time dial settings made for the time-overcurrent

elements The time-overcurrent relay curves in conform to IEEE C37.112-1996 IEEE Standard Inverse-Time

Characteristic Equations for Overcurrent Relays.

IEC Curves:

C1 (Standard Inverse)
C2 (Very Inverse)
C3 (Extremely Inverse)
C4 (Long-Time Inverse)
C5 (Short-Time Inverse)
U.S. Curves:

U1 (Moderately Inverse)
U2 (Inverse)
U3 (Very Inverse)
U4 (Extremely Inverse)
U5 (Short-Time Inverse)




● PC software for controller Testing, Setting, programing, Update.



Human friendship interface Programmable Time-Overcurrent curve

● RPS feature
The high quality 3 mm stainless steel are used for tank, which is designed for its maximum robustness and minimum welding line to minimize corrosion, and specifically to guarantee the safety of the operation personnel even with the internal arc faults at the maximum fault capacity of the tank the RPS can withstands an internal fault without venting hot gases.
The independent spring operation mechanism adopt ROCKWILL® patent spiral spring, provides a guaranteed load break fault make capability by ensuring the opening and closing speed of the switch.
The RPS is provided with light reflecting position indicator which are directly connected to the switch operating shaft providing clear and unambiguous switch position indication. Indicator made of light reflecting material, which is easily visible from ground level even at night in driving rain.
● Main new advantages of RPS
ROCKWILL® Supply special design manual closing device technology with own patent, It applied for normal and abnormal situation closing. It’s closing speed(time) comply with IEC62271-100.
This function can offset from magnetic actuator fault which when actuator can’t work will cause the major accident.
Corrosion resistant, Composite bushingManual lock-out mechanism (including hook stick) Reliable housing groundO/C indicator (made of light reflecting material), Operation counter, Gas density gauge which are easily visible from ground level.
Advanced and Integrated helium leakage detecting and filling equipment, which ensuring SF6 leakage of each switch is less than 0.1% strictly per year.
Motor drive, which easily retrofitted on site to manually operated units.


● Creepage Distances of RPS

Terminal to ground creepage
15kV BIL 95/110kV
27kV BIL125/150kV
38kV BIL 170/200kV
Composite bushing
564mm
840mm
1400mm
Porcelain bushing
556mm
708mm 1250mm


●Current transformer and Voltage sensor

Part Number
RPS-15
RPS-27
RPS-38
Manual
Motorize
Manual
Motorize
Manual
Motorize
Current transformer
/ 3 / 3 / 3
Voltage sensor
/ 3/6 / 3/6 / 3/6

Note: Current transformers and voltage sensors can be customized according to requirements.

●Standards for reference
IEC 62271-1 IEC 62271-102 IEC 62271-103
High-voltage switchgear and controlgear. Part 103: switches for rated voltage above 1 kV up to and including 52 kV

Front: Color clear O/C indicator                                Rear:Highly reliable explosion-proof valve,Inflatable/deflation integrated device

●Technical service
ROCKWILL®, China. Provide with best  support

If you have any question please consult belowTel: 0086-577-27869969
Email: rockwell@rockwill.cn



No.

Name

Unit

RPS-12

RPS-27

RPS-38

1

Rated voltage

kV

12

27

38

2

Rated frequency

Hz

50/60

50/60

50/60

3

Lightning impulse withstand voltage

relatively

kV

75

125

185

Fracture

85

145

215

Power frequency withstand voltage
1min

relatively

kV

42

64

95

Fracture

50

79

110

5

Rated current

A

630(400)

630(400)

630(400)

6

Rated breaking load current (0.07Mpa / 20 ° C)

A

630(400)

630(400)

630(400)

7

breaking current under zero gauge pressure

A

630(400)

630(400)

630(400)

8

peak withstand current

kA

50

50

50

9

Rated short time making current

kA

50

50

50

11

rated short time withstand current

KA/s

20/4

20/4

20/4

12

rated cable charging breaking current

A

25

25

25

13

rated line charging breaking current

A

16

16

16

14

rated closed-loop breaking current

A

630(400)

630(400)

630(400)

15

exciting current

A

21

21

21

16

rated current breaking times

Times

≥400

≥400

≥400

17

rated working pressure

MPa

0.07

0.07

0.25

20

operation of echanical stability

times

6000

6000

6000

21

rated operating voltage and auxiliary circuits rated voltage

V

DC 220/
110/48/24

DC 220/
110/48/24

DC 220/
110/48/24

AC 220/110

AC 220/110

AC 220/110


1, Map guide&location           2, Protection setting&Modification    3, Monitoring&Controlling


●Master software for Distribution Automation Management

About Us
Success References
Best solution for your power!
Copyright © 2018 Rockwill Electric Group Co.,Ltd. All Rights Reserved.