Recloser
Recloser RCW+ RCW+ type auto recloser is a high performance switchgear sealed with…
Recloser

Recloser Recloser Recloser

Detailed description

  • Description
  • Gas type recloser
  • Rockwill Recloser Advantage
  • Recloser Mobile APP software GPRS/GSM/WIFI/BLUETOOTH
  • 11kV 15.5kV recloser dimension
  • 27kV 38kV recloser dimension

Recloser RCW+


RCW+ type auto recloser is a high performance switchgear sealed with SF6 gas. Which is IP67 class switchgear.


RCW+ type auto recloser is DESIGNED For using very important field like key electricity supply points like: gas/oil/mine field, hospital/government/military area, important building etc.


RCW+ Auto recloser is equipped with a manual closing solution which is patent design according to the existing brands recloser problem, like ABB, Schneider, Eaton,Siemens, Hubbel,Noja,Jinkang,ect, these listed brand only offer a normal solution recloser which design cant provide with solution for manual closing with elctric power.


RCW+ auto recose is a fast switching switchgear, standard configuured with magnetic actuator and manual closing and opening/locking device, Max 6 voltage sensors.


RCW+ auto recloser is full complied with standard IEC62271-111, ANSI/IEEE C37.60.


RCW+ auto recloser is Offering:

Voltage Rating: 15kV- 38kV

Current Rating: 630A-1250A

Short circuit breaking: 16kA,..25kA


More informations pls go to study RCW+ manual.


https://www.linkedin.com/company/wenzhou-rockwill-electric-co-ltd-/


RCWF type recloer general specification

● Summary
ROCKWILL ® Electric strives to bring our customers the latest technology and competitive pricing and best service for distribution automatic.
The RCW series automatic circuit reclosers can use on overhead distribution lines as well as distribution substation applications for all voltage classes 11kV up to 38kV at 50/60Hz power system. and it’s rated current can reach 1250A.
The RCW series automatic circuit reclosers integrates the functions of control, protection, measurement, communication, fault detection, on-line monitoring of closing or opening.
● Service environment 1.Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃
Humidity: Monthly average humidity 95%; Daily average humidity 90% .
Altitude above sea level: Maximum installation altitude: 2500m or more higher.
Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. No frequent violent shake
●Offering With optional classes for rated current range:
--Type RCW12, Rating 6-12 kV with 630A, 16 kA up to 1250A, 20kA;
--Type RCW15, Rating15-20 kV with 630A, 16 kA up to 1250A, 20kA;
--Type RCW27, Rating22-27 kV with 630A, 16 kA up to 1250A, 20kA;
--Type RCW38, Rating30-40.5 kV with 630A, 16 kA up to 800A, 20kA;
With optional classes for different grid application installation: Single phase & Three phase.
With optional relay protection& logics for user choice:
+Instantaneous over-current protection.
+Timing over-current protection
+Negative sequence over-current protection.
+Directional over-current protection(*).
+Over-voltage protection./Under voltage protection.
+Programable protection relay curves total 10 nos ANSI/IEC curves.
+Cold load pickup protection TCC +Hot line tag
+Earth protection EF/SEF +Zone Sequence Co-ordination
+More relay functions can be customized.
With optional communication protocols & I/O port for user choice:
RS-232 and RS-485 ports supporting.
DNP3.0 communication protocol support(*).
Modbus communication protocol is optional(*).
IEC 60870-5-101 communication protocol support.
IEC 60870-5-104 communication protocol support.(*).
The recloser can communicate through GPRS(Or GSM) modem with English or Specified language (*).
With optional functions for user.
Rated currents, System phase current.
Rated voltages, System phase voltage& secondary low voltage power supply voltage. Frequency, power(kWh),
reactive power(kV arh), power factor .
With optional reclosing interval for user pre-program:
Reclosing times setting support.
Dead time setting support.
With events recording function:
SOE 10000 operations record.
Fault record and normal operation record.
Note: (*) mean should customized by manufacturer if needed.

●Time-Overcurrent Curves The following information describes the curve timing for the curve and time dial settings made for the time-overcurrent

elements The time-overcurrent relay curves in conform to IEEE C37.112-1996 IEEE Standard Inverse-Time
Characteristic Equations for Overcurrent Relays.

IEC Curves:
C1 (Standard Inverse)
C2 (Very Inverse)
C3 (Extremely Inverse)
C4 (Long-Time Inverse)
C5 (Short-Time Inverse)



U.S. Curves:
U1 (Moderately Inverse)
U2 (Inverse)
U3 (Very Inverse)
U4 (Extremely Inverse)
U5 (Short-Time Inverse)




● PC software for controller Testing, Setting, programing, Update.



Human friendship interface Programmable Time-Overcurrent curve


● Recloser feature a)Outline of recloser:
The RCW series vacuum recloser is mainly combined with integration terminal, current transformer, permanent magnetic actuator and it’s recloser controller.
b)The recloser tank feature:
The Vacuum recloser tanks are manufactured from 304# grade stainless steel and are powder coated a light grey colour. Whole recloser IP67 protection class, equipped with a auxiliary plug to connect with recloser controller by control cable, Diameter Max22mm, 6 M length (8M for special).
It’s can performance serve more than 20 years long term under heavy duty circumstance.
● Main new advantages of RCW High reliable manual opening device High reliable manual closing device


Visible ON/OFF indicator                               IP67 class waterproof plug connector
ROCKWILL ® Supply special design manual closing device technology with own patent, It applied for normal and abnormal situation closing. It’s closing speed(time) comply with IEC62271-100. This function can offset from magnetic actuator fault which when actuator can’t work will cause the major accident.

---------------------------------------------

Primacy incomer terminal (directly connect to interrupter reduce power lost) Current sensor (external modular design easy for quality control and maintenance) Accuracy: ±0.5% Ratio:800/1

Internal Voltage sensors incorporated within the vacuum interrupter module. Accuracy: ±0.2 % Voltage Sensor, Ratio:500/1 or 1000/1.

It’s equipped with two voltage sensors, one for measuring the voltage of incoming side, and another one for measuring the voltage of outgoing side.

● Creepage Distances of RCW

Description
12kV BIL
75/95kV
15kV BIL
95/110kV
27kV
BIL125/150kV
38kV BIL
170/200kV
Terminal to terminal creepage
600mm
840mm
1250mm
1380mm


Terminal to ground creepage
510mm
760mm
1200mm
1300mm


Apply ANSOFT design the high performance magnetic actuator, high reliable and free maintenance. Through 35,000 times opening reverse excitation test, the demagnetization rate less than 1%.

Note:

ROCKWILL? supply special patent modular design mono-stable type magnetic actuator with two coils controlling. It’s the best design for vacuum circuit breaker.








● Main technical data

N Item
Unit
Data
1 Rated max voltage
kV 12 15 27 38
2 Rated current
A 630/800/1250
3 Rated frequency
HZ 50/60
4
Power frequency 1min
Dry
kV
45 55 65 95
Wet
30 45 55 80
5 Lightning impulse withstand voltage(peak)
kV 75/95*
95/100*
125/150*
170/200*
6 Rated short circuit breaking current
kA 12.5/16/20/25*
7 Rated short current switching current(peak)
kA 31.5/40/50/63*
8 Rated peak value withstand current
kA 31.5/40/50/63*
9 4S short time withstand current
kA 12.5/16/20/25*
11 Rated operating circulate

O-0.5S-CO-2S-CO-2S-CO
10 Breaking current frequency under rated short circuit
time 200
12 Mechanism life
time 10000
13 Secondary loop 1 min power frequency withstand
kV 2
14 Auxiliary voltage supply
Vac 220±20%
15 Battery bank
Vdc 12×2
16 Capacitor unit
Vdc 220


●Accessories of RCW

All above insulating components for BIL 200kV expanding using. Any question please contact with our engineer.



Upper voltage shield 3 pcs/set


Terminal 6 pcs/set

Standard made of T2 copper material, for 630/1250A rated current using. With  expanding range.


●Technical service
ROCKWILL?, China. Provide with best support.
If you have any question please consult below:
Tel: 0086-577-27869969
Email: rockwell@rockwill.cn




The main Feature of RCW+ type gas type auto recloser


1,SF6 gas insulated, IP67 class

2,Magnetic actuator with Manual closing device and manual opening/Locking

3,Outdoor epoxy resin bushing with max 6 nos voltage sensor

4,Manufacturing under per standard of IEC62271-111 & ANSI/IEEE C37.60

5,RKW352 controller with 10 nos IEC/ANSI curves

6,Programable software for auto recloser

7,Ready for WIFI/BULETOOTH/GRPS/GSM communication

8,Additional functions: Mechanical life counter, elctrical life counter by software

9,Offer more relay protection functions and more communication protocols


1. One-stop supplier globally.
2. More than 10 years professional experiences in electrical appliance industry. 
3. We offer professional online technology support for perfecting your electrical solution free.
4. Experienced sales service and suggestion.
5. All the products with accessories under strict quality control and final inspection before shipping.
6. We can assure the powerful competitive price and reliable quality products.
7. Most competitive shipping rate from our own shipping forwarder.
8. Warranty assurance: 12 months, Offer according to special request 

9. Whatever big or small order, we can provide you one-to-one service.

OUR SERVICE:
1.quick response in before sales period help you got order.
2.excellent service in production time let you know each step we made.
3.reliable quality solve you after sale headache.
4.long period quality warranty ensure you can buy without hesitate.

CONTACT US:
Contact person: Mr. Chen Chengming
Mobile/Whatsapp:+86-18668777248


1, Map guide&location           2, Protection setting&Modification    3, Monitoring&Controlling


  

●Master software for Distribution Automation Management

 

Best solution for your power!