Single phase recloser
Single phase recloser RCW(T) Type auto recloser is a pole mounted singlle phase sw…
Single phase recloser

Single phase recloser Single phase recloser Single phase recloser

Detailed description

  • Description
  • Technical data
  • 8.6kV auto reloser
  • 15.6kV auto reloser
  • 22kV auto reloser

Single phase recloser


RCW(T) Type auto recloser is a pole mounted singlle phase switchgear. Equipped with stainless steel tank, Current sensor and voltage sensor and RKW351 RECLOSER CONTROLLER.

RCW(T) Type auto recloser is a high performance design, which equipped with a magnetic actuator and opening/locking device.

it can be used on overhead distribution lines applications for all voltage classes 8.6kV up to 23kV at 50/60Hz single wire grid.

RCW(T) Type single pole or single phase auto recloser is complied with standard: IEC62271-111,ANSI/IEEC C37.60 and GB1984-2006.

RCW(T) Type ingle pole or single phase auto recloser is aviable for SCADA with own Smart APP software, its ready for WIFI/Buletooth/GPRS/GSM communication.

More details information please check with us.


Summary
ROCKWILL® Electric strives to bring our customers the latest technology and competitive pricing and best service for distribution automatic.
The RCW-1 series automatic circuit reclosers can use on overhead distribution lines as well as distribution substation applications for all voltage classes 8.6kV up to 22kV at 50/60Hz power system. and it’s rated current can reach 1250A.
The RCW-1 series automatic circuit reclosers integrates the functions of control, protection, measurement, communication, fault detection, on-line monitoring of closing or opening.


Service environment
1.Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃
Humidity: Monthly average humidity 95%; Daily average humidity 90% .
Altitude above sea level: Maximum installation altitude: 2500m or more higher.
Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
No frequent violent shake


Offering
With optional classes for rated current range:
For 8.6kV, with 630A, 20kA Breaking capacity. 800A, 20kA capacity, and 1250A, 20kA.
For 15.6V, with 630A, 20kA Breaking capacity. 800A, 16kA capacity, and 1250A, 25kA.
For 22kV, with 800A, 20kA, And expanding 1250A, .25kA RCW-1-22M type.
With optional classes for installation styles:
Single phase, vacuum recloser and Three phase, vacuum recloser.
With optional relay protection curves for user choice:
Instantaneous over-current protection.
Timing over-current protection.
Negative sequence over-current protection.
Directional over-current protection(*).
Over-voltage protection./Under voltage protection.
More relay functions can be customized.
With optional choice by locally or remotely.
With optional communication protocols & I/O port for user choice:
RS-232 and RS-485 ports supporting.
DNP3.0 communication protocol support(*).
Modbus communication protocol is optional(*).
IEC 60870-5-101 communication protocol support.
IEC 60870-5-104 communication protocol support.(*).
The recloser can communicate through GPRS(Or GSM) modem with English or Chinese language (*).
With optional functions for user.
Rated currents, System phase current.
Rated voltages, System phase voltage& secondary low voltage power supply voltage. Frequency, power(kWh), reactive power(kV arh), power factor .
With optional reclosing interval for user pre-program:
Reclosing times setting support.
Dead time setting support.
With events recording function:
SOE 1000 operations record.
Fault record and normal operation record.
Note: (*) mean should customized by manufacturer if needed.

Recloser feature
a)Outline of recloser:
The RCW-1 series vacuum recloser is mainly combined with integration terminal, current transformer, permanent magnetic actuator and it’s recloser controller.
b)The recloser tank feature:
The Vacuum recloser tanks are manufactured from 304# grade stainless steel and are powder coated a light grey colour. Whole recloser IP65 protection class, equipped with a auxiliary plug to connect with recloser controller by control cable, Diameter Max22mm, 6 M length (8M for special). It’s can performance serve more than 20 years long term under heavy duty circumstance.


Creepage Distances of RCW-1

Description
8.6kV BIL 95/110kV
15.6kV BIL125/150kV
22kV BIL 170/200kV
Terminal to terminal creepage
600mm
840mm
1250mm





ROCKWILL®

Supply special design manual closing devicetechnology with own patent, It applied for normal and abnormal situation closing. It’s closing speed(time) comply with IEC62271-100. This function can offset from magnetic actuator fault which when actuator can’t work will cause the major accident.

Primacy incomer terminal (directly connect to interrupter reduce power lost)
Current sensor (external modular design easy for quality control and maintenance) Accuracy: ±0.5% Ratio:800/1

Vacuum interrupter (Adopt the APG technology, increasing the whole insulation and weathering performance)

Internal Voltage sensors incorporated within the vacuum interrupter module It’s equipped with two voltage-sensors, one for measuring the voltage of incoming side, and another one for measuring the voltage of outgoing side.

Shielded 4-conductor cable connection Voltage Sensor Accuracy: ±0.2 % Voltage Sensor Ratio:500/1 or 1000/1

High reliable manual opening device

Visible ON/OFF indicator and Counter

IP64 class waterproof plug connector

Apply ANSOFT design the high performance magnetic actuator, high reliable and free maintenance. Through 35,000 times opening reverse excitation test, the demagnetization rate less than 1%.








Note:

ROCKWILL? supply special patent modular design mono-stable type magnetic actuator with two coils controlling. It’s the best design for vacuum circuit breaker.







●Accessories of RCW

All above insulating components for BIL 200kV expanding using. Any question please contact with our engineer.







Upper voltage shield 3 pcs/set






Terminal 6 pcs/set

Standard made of T2 copper material, for 630/1250A rated current using. With  expanding range.


●Technical service
ROCKWILL?, China. Provide with best support.
If you have any question please consult below:
Tel: 0086-577-27869969
Email: rockwell@rockwill.cn


N

Item

Unit

Data

1

Rated voltage

kV

8.6

15.6

22

2

Rated current

A

630

630/1250

630/1250

3

Rated frequency

Hz

50/60

4

Power frequency 1min

Dry

kV

36

50

60

Wet

30

45

50

5

Lightning impulse withstand voltage(peak)

kV

75

125/150

150

6

Rated short circuit breaking current

kA

16

16

12.5

7

Rated short current switching current(peak)

kA

40

40

31.5

8

Rated peak value withstand current

kA

40

40

31.5

9

4S short time withstand current

kA

16

16

12.5

11

Rated operating circulate


O-0.5S-CO-2S-CO-2S-CO-20S-CO

10

Breaking current frequency under rated short circuit

time

200

12

Mechanism life

time

10000

13

Secondary loop 1 min power frequency withstand

kV

2