Project Overview

After the commissioning of a 126kV power project featuring triple-break vacuum dead tank circuit breakers, electric field simulation testing revealed a severe imbalance in voltage distribution across the breaks (74% at the high-voltage end, 19% in the middle, and 7% at the low-voltage end). The electric field intensity at the metal connectors reached 18kV/mm (exceeding the safety threshold by 5 times). After only 6 months of operation, abnormal partial discharge (PD) noises occurred at the high-voltage end interrupter, posing risks of insulation aging and interruption failure. Leveraging 3D electric field simulation technology, our company completed the reconstruction of the voltage grading system within 7 days: replacing the existing structure with a cylindrical grading capacitor design and precisely matching the capacitance parameters. Post-governance, the voltage distribution uniformity improved to 93%, electric field intensity dropped to 2.6kV/mm, and PD signals returned to zero. The equipment has operated stably for over 24 months, ensuring the safe operation of the project.

Exceptional Design · Root Cause Eradication

Focusing on the trinity of "Simulation-Driven - Structural Reconstruction - Precise Parameters":

  • 3D Simulation Priority: Established a refined electric field model for the 126kV triple-break system to precisely locate floating potentials and electric field concentration points, providing quantitative calculations for the optimal grading solution.

  • Structural Reconstruction & Upgrade: Replaced bilateral grading capacitors with an integrated cylindrical design, optimizing the layout of conductive rods and shields to reduce stray capacitance by 35%.

  • Precise Parameter Matching: Customized grading capacitor values ensured that the voltage distribution uniformity across the breaks reached ≥ 90%, with electric field intensity strictly controlled within the safety threshold of ≤3 kV/mm.

Empowering Infrastructure Development

This case led to the development of the "Technical Guidelines for the Design and Verification of Voltage Grading Systems in High-Voltage Dead Tank Circuit Breakers," which has been promoted across 18 key 126kV/252kV projects nationwide, averting 29 electric field concentration hazards. Through a closed-loop technical system of "Simulation-Design-Verification," our company is driving circuit breaker grading design from an experience-oriented approach to precise quantification. This provides core support for enhancing the reliability of extra-high-voltage equipment and contributes to the construction of a safe and resilient new power system.


Related Articles

...
Rockwill 2500kVA Step up Transformer Success in Namibia
Rockwill 2500kVA Step up Transformer Success in Namibia
Rockwill 2500kVA transformers support Namibia 20MW PV plant with high-altitude insulation and C5-M anti-corrosion, reducing maintenance costs by 35%.
Successful Case of 263 Units of 33kV Oil-immersed 32-step Voltage Regulator Controller Project in Bangladesh
Successful Case of 263 Units of 33kV Oil-immersed 32-step Voltage Regulator Controller Project in Bangladesh
Rockwill delivered 263 units of 33kV 32-step voltage regulators in Bangladesh. Proven reliability for grid stability. View our technical success story.
Rockwill RGIS Case Study and Gas Insulated Switchgear Project in Ghana
Rockwill RGIS Case Study and Gas Insulated Switchgear Project in Ghana
Read the Rockwill RGIS project success in Ghana providing reliable gas insulated switchgear solutions for enhanced power distribution and grid performance across the region.
Successful Case of 170 Sets of 11kV Automatic Recloser Project in Kenya
Successful Case of 170 Sets of 11kV Automatic Recloser Project in Kenya
170 sets of 11kV automatic recloser project success in Kenya, demonstrating reliable grid automation and enhanced power distribution performance.
Rockwill Ukraine 186 Units 12kV Outdoor Vacuum Recloser Project Success Case
Rockwill Ukraine 186 Units 12kV Outdoor Vacuum Recloser Project Success Case
Rockwill successfully delivered 186 units of 12kV outdoor vacuum reclosers for Ukraine’s distribution network, solving issues like thunderstorms and large temperature differences with intelligent reclosing technology.
Rockwill 400 Units Prefabricated Substation Case Study in Niger
Rockwill 400 Units Prefabricated Substation Case Study in Niger
Rockwill delivered 20kV prefabricated substations to Niger NIGELEC, IEC 62271-202, IP54, French-labeled for Sahel electrification.
Case Study of Rockwill 72.5kV Dead Tank Circuit Breaker Project in South Africa
Case Study of Rockwill 72.5kV Dead Tank Circuit Breaker Project in South Africa
Rockwill 72.5kV Dead Tank Circuit Breaker success case in South Africa providing low maintenance 4000A HV switchgear solutions with built in CTs and 450kV BIL insulation for South African Eskom and mining power networks
Rockwill Intelligent Voltage Regulator Empowers Power Quality Improvement in an Industrial Park in Southeast Asia
Rockwill Intelligent Voltage Regulator Empowers Power Quality Improvement in an Industrial Park in Southeast Asia
Rockwill Intelligent Voltage Regulator empowers power quality improvement in Southeast Asia industrial park with ±0.5% accuracy, ≤1s response & IP54 protection for stable industrial operation.
WhatsApp E-mail Message