have adopted series of important reforms on the 110kV level three-phase oil-immersed on-loadtap changing transformer referring material, process and structure. The transformer has the features of small size, light weight, high efficiency, low loss, low noise, reliable operation etc. which can reduce a large amount of power network loss and operation expense with significant economic benefits. It is suitable for power plant, substation, heavy section plant or enterprises etc.
1. Type: outdoor
2. Ambient temperature: max. temperature: +40℃; min. temperature: -30℃
3. Altitude: ≤1000m (temperature rise shall be corrected when>1000m)
4. Relative humidity: ≤90% (25℃)
5. Installation place: without corrosive gas and apparent fouling.
110kVThree-phase Double-windingNLTCPowerTransformer
Rated Capacity(KVA) |
Voltage ratio |
Vector group |
No-load loss(KW) |
load loss(KW) |
No-load current(%) |
Short circuit impedance(%) |
HV |
LV |
6300 |
110±2*2.5%;
115±2*2.5%;
121±2*2.5%;
|
6.3;
6.6;
10.5
|
YNd11 |
7.4 |
35 |
0.62 |
10.5 |
8000 |
8.9 |
42 |
0.62 |
10000 |
10.5 |
50 |
0.58 |
12500 |
12.4 |
59 |
0.58 |
16000 |
15 |
73 |
0.54 |
20000 |
17.6 |
88 |
0.54 |
25000 |
20.8 |
104 |
0.5 |
31500 |
24.6 |
123 |
0.48 |
40000 |
29.4 |
148 |
0.45 |
50000 |
35.2 |
175 |
0.42 |
63000 |
41.6 |
208 |
0.38 |
75000 |
13.8;
15.75;
18;
21
|
47.2 |
236 |
0.33 |
12~14 |
90000 |
54.4 |
272 |
0.3 |
120000 |
67.8 |
337 |
0.27 |
150000 |
80.1 |
399 |
0.24 |
180000 |
90 |
457 |
0.2 |
110kVThree-phase Three-windingNLTCPowerTransformer
Rated Capacity(KVA) |
Voltage ratio |
Vector group |
No-load loss(KW) |
load loss(KW) |
No-load current(%) |
Short circuit impedance(%) |
HV |
LV |
Step up |
Step down |
6300 |
110±2*2.5%;
115±2*2.5%;
121±2*2.5%;
|
6.6;
11;
24
|
YNyn0d11 |
8.9 |
44 |
0.66 |
HV-MV:17.5~18.5;
HV-LV:10.5;
MV-LV:6.5
|
HV-MV:10.5;
HV-LV:18~19;
MV-LV:6.5
|
8000 |
10.6 |
53 |
0.62 |
10000 |
12.6 |
62 |
0.59 |
12500 |
14.7 |
74 |
0.56 |
16000 |
17.9 |
90 |
0.53 |
20000 |
21.2 |
106 |
0.53 |
25000 |
24.6 |
126 |
0.48 |
31500 |
29.4 |
149 |
0.48 |
40000 |
34.8 |
179 |
0.44 |
50000 |
41.6 |
213 |
0.44 |
63000 |
49.2 |
256 |
0.4 |
110kVThree-phase Double-windingOLTCPowerTransformer
Rated Capacity(KVA) |
Voltage ratio |
Vector group |
No-load loss(KW) |
load loss(KW) |
No-load current(%) |
Short circuit impedance(%) |
HV |
LV |
6300 |
110±8*1.25%; |
6.3;
6.6;
10.5;
21
|
YNd11 |
8 |
35 |
0.64 |
10.5 |
8000 |
9.6 |
42 |
0.64 |
10000 |
11.3 |
50 |
0.59 |
12500 |
13.4 |
59 |
0.59 |
16000 |
16.1 |
73 |
0.55 |
20000 |
19.2 |
88 |
0.55 |
25000 |
22.7 |
104 |
0.51 |
31500 |
27 |
123 |
0.51 |
40000 |
32.3 |
156 |
0.46 |
12~18 |
50000 |
38.2 |
194 |
0.46 |
63000 |
45.4 |
232 |
0.42 |
110kV Three-phase Three-winding OLTC Power Transformer
Rated Capacity(KVA) |
Voltage ratio |
Vector group |
No-load loss(KW) |
load loss(KW) |
No-load current(%) |
Short circuit impedance(%) |
HV |
MV |
LV |
6300 |
110±8*1.25%; |
36 |
6.6;11;24 |
YNyn0d11 |
9.6 |
44 |
0.76 |
HV-MV:10.5;
HV-LV:18~19;
MV-LV:6.5
|
8000 |
11.5 |
53 |
0.76 |
10000 |
13.6 |
62 |
0.71 |
12500 |
16.1 |
74 |
0.71 |
16000 |
19.3 |
90 |
0.67 |
20000 |
22.8 |
106 |
0.67 |
25000 |
27 |
126 |
0.62 |
31500 |
32.1 |
149 |
0.62 |
40000 |
38.5 |
179 |
0.58 |
50000 |
45.5 |
213 |
0.58 |
63000 |
54.1 |
256 |
0.53 |
66kV Three-phase PowerTransformerwith 0ff-loadTapChanger
Rated power(KVA) |
Hve(KV) |
Tap(KV) |
LV(KV) |
Vector group |
Short circuit impedance(%) |
No-load loss(W) |
On-load loss(%) |
No-load current(%) |
The 9 type of loss |
The 10 type of loss |
The 11 type of loss |
The 9 type of loss |
The 10 type of loss |
The 11 type of loss |
6300 |
63;
66;
69
|
±2*2.5% |
6.3;
6.6;
10.5;
11;
13.2;
15
|
YNd11 |
9 |
9.5 |
8.5 |
7.5 |
26 |
34 |
34 |
0.63 |
8000 |
11.4 |
10.2 |
9 |
42.8 |
40.4 |
40.4 |
0.63 |
10000 |
13.5 |
12.1 |
12.1 |
50.4 |
47.6 |
47.6 |
0.75 |
12500 |
15.9 |
14.2 |
12.6 |
59.9 |
56.5 |
56.5 |
0.53 |
16000 |
19.1 |
17.1 |
15.1 |
73.53 |
69.5 |
69.5 |
0.49 |
20000 |
22.6 |
20.3 |
17.9 |
89.1 |
84.2 |
84.2 |
0.49 |
25000 |
26.7 |
23.9 |
21.1 |
105.3 |
99.5 |
99.5 |
0.42 |
31500 |
31.8 |
28.4 |
25.1 |
126.9 |
120 |
120 |
0.42 |
40000 |
38 |
34 |
30 |
148.5 |
140.3 |
140.3 |
0.39 |
50000 |
44.9 |
40.1 |
35.4 |
184.5 |
174.3 |
174.3 |
0.39 |
63000 |
53.3 |
47.7 |
42.1 |
222.3 |
210 |
210 |
0.39 |
66kV Three-phase PowerTransformerwith On-loadTapChanger
Rated power(KVA) |
Hve(KV) |
Tap(KV) |
LV(KV) |
Vector group |
Short circuit impedance(%) |
No-load loss(W) |
On-load loss(%) |
No-load current(%) |
The 9 type of loss |
The 10 type of loss |
The 11 type of loss |
The 9 type of loss |
The 10 type of loss |
The 11 type of loss |
6300 |
63;
66;
69
|
±8*1.25% |
6.3;6.6;10.5;11;13.2;15 |
YNd11 |
9 |
10.5 |
9.4 |
8.25 |
36 |
34 |
34 |
0.63 |
8000 |
12.5 |
11.2 |
9.83 |
42.8 |
40.4 |
40.4 |
0.63 |
10000 |
14.7 |
13.1 |
11.6 |
50.4 |
47.6 |
47.6 |
0.75 |
12500 |
17.2 |
15.4 |
13.6 |
59.9 |
56.5 |
56.5 |
0.53 |
16000 |
20.6 |
18.5 |
16.3 |
73.53 |
69.5 |
69.5 |
0.49 |
20000 |
24.3 |
21.8 |
19.2 |
89.1 |
84.2 |
84.2 |
0.49 |
25000 |
28.6 |
25.6 |
22.6 |
105.3 |
99.5 |
99.5 |
0.42 |
31500 |
33.9 |
30.4 |
26.8 |
126.9 |
120 |
120 |
0.42 |
40000 |
40.4 |
36.2 |
31.9 |
148.5 |
140.3 |
140.3 |
0.39 |
50000 |
47.8 |
42.6 |
38.6 |
184.5 |
174.3 |
174.3 |
0.39 |
63000 |
56.3 |
50.4 |
44.4 |
222.3 |
210 |
210 |
0.39 |