Single phase pole mounted distribution transformers
Product Description:
Single phase pole mounted distribution transformers are designed and manufactured in compliance with all applicable ANSI and IEC standards. All transformers are oil filled, 65˚C rise,and designed for usual service conditions per ANSI C57.12.00. External welds are 100% coverage for added strength and corrosion withstand. Lift ears allow sling lifting while the unit is still banded to the pallet. The tank bottom weld is recessed for added protection.
| Technical Data of D9 Series Single Phase Distribution Transformer |
| |
Voltage Group(kV) |
|
Loss (kW) |
No-load current |
Impedance |
Weight (kg) |
Outline Dimension (mm) |
Gauge |
| Rated Capacity |
Connection Method |
| (L) |
(W) |
(H) |
|
| (kVA) |
HV |
LV |
|
No-load |
Load |
% |
% |
Machine |
Oil |
Gross |
Dimension |
Vertical |
Horizontal |
| 5 |
13.8 |
0.22 0.24 |
|
35 |
145 |
4 |
3.5 |
50 |
40 |
130 |
530 |
450 |
850 |
400 |
250 |
| 10 |
13.2 |
|
55 |
260 |
3.5 |
65 |
40 |
150 |
560 |
450 |
870 |
400 |
300 |
| 16 |
11 |
|
65 |
365 |
3.2 |
80 |
40 |
180 |
600 |
450 |
920 |
400 |
300 |
| 20 |
10.5 |
|
80 |
430 |
3 |
100 |
50 |
205 |
620 |
450 |
940 |
400 |
300 |
| 30 |
10 |
li0 |
100 |
625 |
2.5 |
115 |
50 |
225 |
700 |
450 |
980 |
400 |
300 |
| 40 |
li6 |
125 |
775 |
2.5 |
150 |
55 |
270 |
700 |
480 |
970 |
400 |
300 |
| 50 |
6.3 |
|
150 |
950 |
2.3 |
175 |
70 |
310 |
650 |
510 |
1100 |
400 |
300 |
| 63 |
6 |
|
180 |
1135 |
2.1 |
190 |
80 |
340 |
660 |
520 |
1100 |
400 |
300 |
| 80 |
|
|
200 |
1400 |
2 |
240 |
100 |
420 |
770 |
630 |
1120 |
450 |
300 |
| 100 |
|
|
240 |
1650 |
1.9 |
295 |
100 |
490 |
840 |
600 |
1150 |
450 |
300 |
| 125 |
|
|
285 |
1950 |
1.8 |
370 |
110 |
560 |
890 |
740 |
1160 |
500 |
400 |
| 160 |
|
|
365 |
2365 |
1.7 |
430 |
130 |
650 |
950 |
790 |
1170 |
500 |
400 |
Remarks: Normal Type No protection accessories.
CP Type with HV Load switch, HV fuse and LV over-current CB
SP Type: With HV load switch, HV fuse and surge arrestor
CSP Type: With HV load switch, HV fuse, surge arrestor and LV over-current CB

1. Altitude: <1000m indoor
2. Max .ambient: temperature +40℃
3.Max. daily: average temperature +30℃
4.Max .annual: average temperature +20℃
5.Min. temperature -5℃
6.Supply transformer operate under special conditions according to customer requirements.