Indoor fixed type vacuum circuit breaker
General: The vacuum circuit-breakers of type VD4/S are intended for indoor ...

Detailed description

  • Description
  • Technical data
  • Guideline values for function times

General:
The  vacuum  circuit-breakers  of  type  VD4/S  are  intended  for  indoor  installation  in  air-insulated switchgear  systems.  They  have  a  switching  capacity  capable  of  handling  the  loads  occurring  at start-up and shutdown of equipment and plant units both in normal and in fault state.Vacuum  circuit-breakers  have  particular  advantages  for  use  in  networks  where  there  is  a  high switching  frequency  in  the  working  current  range  and/or  where  a  certain  number  of  short-circuit breaking  operations  are  expected.  Type  VD4/S  vacuum  circuit-breakers  are  suitable  for autoreclosing, and have exceptionally high operating reliability and long life. The  vacuum  circuit-breakers  of  type  VD4/S,  designed  in  column  form,  can  be  supplied  both  as individualunits for switchgear T ype SM6, Uniswitch, HXGN, etc.
 

Standards and specifications
Switchgear manufacture
The  switchgear  complies  with  the  following  specifications  in  accordance  with  DIN,VDE  and  the relevant IEC publications:
• VDE0670, part1000 and IEC60694
• VDE0671, part100, and IEC62271-100.
• GB1984-2003
Installation  and  operation  The  relevant  specifications  are  to  be  taken  into  account  during installation and operation, particularly:
• DIN VDE0101, Power installations exceeding  AC1 kV
• VDE0105, Operationof electrical installations
• DIN VDE0141, Earthing systems for special power installations with rated voltages above1 kV
•  Accident  prevention  regulations  issued  by  the  appropriate  professional  bodies  or  comparable organizations.
 

Operating conditions
Normal  operating  conditions  Design  to  VDE  0670,  part  1000,  “Common  specifications  for high-voltage switchgear and controlgear standards“ and IECpublication60694, with the following limit values:
•  Ambient temperature:
–Maximum +40℃
–Maximum24 hour average +35℃
–Minimum (according to “minus5 indoor class”) –5℃
• Humidity:
–the average value of the relative humidity , measured over a periodof24 h, doesnot exceed95%
–the average value of the water vapour pressure, over a period of24 h, does not exceed2,2 kPa
–the average value of the relative humidity , over a period of one month, does not exceed90%
–the  average  value  of  the  water  vapour  pressure,  over  a  period  of  one  month,  does  not  exceed  1,8 kPa
• Maximum site altitude: ≤1000 M above sea level.
Specialoperating conditions:
Special operating conditions are to be agreed onby the manufacturer and user . The manufacturer must be consulted in advance about each specialoperating condition:
• Site altitude over1000 m:
–Allow for the reduction in the dielectric strengthof the air .
• Increased ambient temperature:
–Current carrying capacity is reduced.
–Provide additional ventilation for heatdissipation.
• Climate:
–A void the risk of corrosion or other damage in areas:
• with high humidity and/or
• with major rapid temperature fluctuations.
–  Implement preventive measures (e.g. electric heaters) to preclude condensation phenomena

No.
Item
Unit
Parameters
1
Rated voltage
kV
12/17.5
24
2
Rated frequency
Hz
50/60
3
Rated current
A
630/800/1250/1600
4
1min Power frequency withstand voltage
kV
38/42/45
50
5
Lightning impulse withstand voltage
kV
75/95
125/150(*)
6
Rated short circuitbreaking current (peak)
kA
50/63/80
7
Rated shortbreaking current
kA
20/25/31.5
8
Rated short circuit making current (peak)
kA
50/63/80
9
Cable chargebreaking current in earthing fault
A
20
20
10
Rated withstand current (peak)
kA
50/63/80
11
Short time withstand current (4s)
kA
20/25/31.5
12
Mechanism life
times
10000
13
Operation sequence
 
 
 
O-0.3-CO-180S-CO
 
14
Rateof riseof transient recovery voltage
kV/uS
0.34/0.42
0.47
15
Peak of transient recovery voltage
kV
20.6/30
41
No
Item
Unit
Parameter
1
Closing time approx
ms
60ms
2
Opening time approx
ms
Less than45ms
3
Arcing time (at50Hz)
ms
Less than15ms
4
Breaking time
ms
Less than 60 ms
Minimum command
 
5
T ime on closing
ms
20ms(¹)(120ms(²))
35ms(¹)(70ms(²))
6
Time on opening
ms
20ms(¹)(80ms(²))
20ms(¹)(50ms(²))