Cost effective: peak shaving and valley filling, efficient conversion, deep power supply, seamless switching
Safe: real-time monitoring, perfect mechanism, multi-level protection, comprehensive management
Intelligent: multiple modes, intelligent control, real-time monitoring, rapid response
Technical indicators |
RW525KWH-250 |
RW1051KWH-250 |
|
Battery Parameter |
Battery Model |
3.2V120Ah |
3.2V120Ah |
System Battery Configuration |
228S6P |
228S12P |
Rated Capacity |
525kWh |
1051kWh |
Voltage Range |
616-832V |
616-832V |
BMS Communication Interface |
Ethernet,RS485 |
Ethernet,RS485 |
BMS Protocol |
Modbus RTU,Modbus TCP |
Modbus RTU,Modbus TCP |
|
AC Side Parameter |
Rated Power |
250kVA |
250kVA |
MAX OUTPUT |
275kVA |
275kVA |
THID |
<3%(At rated power) |
<3%(At rated power) |
DC Component |
<0.5%(At rated power) |
<0.5%(At rated power) |
Rated Output Voltage |
400V |
400V |
Grid Voltage Range |
310-450V |
310-450V |
Power Factor |
>0.99(At rated power) |
>0.99(At rated power) |
Adjustable Range of Power Factor |
0.9(Leading)-0.9(Lagging) |
0.9(Leading)-0.9(Lagging) |
Rated Grid Frequency |
50Hz |
50Hz |
Power Grid Frequency Range |
45-55Hz |
45-55Hz |
Isolation Way |
Transformer Isolation |
Transformer Isolation |
Off Grid Rated Output Voltage |
400V |
400V |
Distortion Rate of Off Grid Output Voltage |
<3%(Linear Load) |
<3%(Linear Load) |
|
System Parameter |
Inverter Carton Size |
600*900*1500mm |
600*900*1500mm |
Battery Container Size |
600*600*2000mm |
600*600*2000mm |
Weight of Converter Container |
2.8T |
2.8T |
Weight of battery container (With battery/Without battery) |
9.6T/5.0T |
(9.6T/5.0T)*2 |
IP Code |
IP54 |
IP54 |
Operating Temperature Range |
-30~+50℃ |
-30~+50℃ |
Operating Humidity Range |
0~95%(Non-condensing) |
0~95%(Non-condensing |
Max Working Altitude |
2000m (>2000m Frequency reduction required) |
2000m (>2000m Frequency reduction required) |
Battery Temperature Control Mode |
Industrial temperature controlled air conditioner |
Industrial temperature controlled air conditioner |
Inverter Cooling Mode |
Temperature controlled forced air cooling |
Temperature controlled forced air cooling |
Fire Alarm System(Battery Container) |
FM200 |
FM200 |
System Communication Interface |
Ethernet,RS485 |
Ethernet,RS485 |
System Communication Protocol |
Modbus RTU,Modbus TCP,IEC 104 |
Modbus RTU,Modbus TCP,IEC 104 |